Goodman Heat Pump Troubleshooting

The tables below are the lists of possible issues which you may encounter having Goodman heat pump not working. There are the descriptions for different Goodman modifications – GPC1336M41, R 410A, and N2H3.

The tables contain symptoms (heat pump not cooling), possible causes and remedies for them. In case, for instance, of heat pump fan not spinning properly, you may do some things to fix the problem without doing the repair.

If the symptom and description show that the heat pump needs serious repair, or the actions described are too complicated for you, do not do it by yourself and call the specialist to do it.

Goodman GPC1336M41 Heat Pump Troubleshooting

SYMPTOMPOSSIBLE CAUSEREMEDY
High head - low suctiona. Restriction in liquid line or flowratora. Remove or replace with proper size flowrator.
High head - high or normal suctiona. Dirty condenser coia. Clean coil.
b. Overchargedb. Correct System charge.
c. Condenser fan not runningc. Repair or Replace.
Low head - high suctiona. Incorrect flowratora. Replace with correct flowrator.
b. Defective compressor valvesb. Replace compressor.
c. Flowrator not seating properlyc. Check for debris under flowrator or deformed flowrator. Remove debris or replace flowrator.
d. Defective reversing valved. Replace reversing valve.
Unit will not runa. Power off or loose electrical connectiona. Check for unit voltage at contactor in unit.
b. Thermostat out of calibration set too highb. Reset.
c. Defective contactorc. Check for 24 volts at contactor coil replace if contacts are open.
d. Blown fuses or tripped breakerd. Replace fuse or reset breaker.
e. Transformer defectivee. Check wiring - replace transformer.
f. High or low pressure control open (Optional)f. Reset high pressure control or check unit charge. High pressure control opens at 610 psig. Low pressure control opens at 22 psig.
g. Compressor overload contacts openg. Replace compressor.
NOTE: Wait at least 2 hours for overload to reset.
Condenser fan runs, compressor doesn’ta. Loose connectiona. Check for unit voltage at compressor check & tighten all connections.
b. Compressor stuck, grounded or open vending open internal overloadb. Wait at least 2 hours for overload to reset If still open, replace the compressor.
c. Low voltage connectionc. At compressor terminals, voltage must be within 10 % of nameplate volts when unit is operating.
d. Capacitor weak, open, or shortedd. Check capacitor. If defective, replace.
Low suction - cool compressor Iced evaporator coila. Low indoor airflowa. Increase speed of blower or reduce restriction - replace air filters.
Compressor short cyclesa. Defective overload protectora. Replace - check for correct voltage.
b. Unit cycling on low pressure controlb. Check refrigerant charge and/or airflow.
Registers sweata. Low airflowa. Increase speed of blower or reduce restriction replace air filters.
High suction pressurea. Excessive loada. Recheck load calculation.
b. Defective compressorb. Replace.
c. Reversing valve not seating properly.c. Replace.
Insufficient coolinga. Improperly sized unita. Recalculate load.
b. Improper airflowb. Check - shouId be approximately 400 CFM per ton.
c. Incorrect refrigerant charge.c. Charge per procedure attached to unit service panel.
d. Incorrect voltaged. At compressor terminals, voltage must be within 10% of nameplate volts when unit is operating.

Goodman R 410A Heat Pump Troubleshooting

SymptomDescrCauseActionCautions
- Motor rocks slightly when starting.- This is normal start-up for variable speed motor.
- Motor won't start.- No movement.- Manual disconnect switch off or door switch open.- Check 230 Vac power at motor.- Turn power OFF prior to repair.
- Blown fuse or circuit breaker.- Check low voltage (24 Vac R to C) at motor.Wait 5 minutes after disconnecting power before opening motor.
- 24 Vac wires miswired.- Check low voltage connections (G, Y, W, R, C) at motor.- Handle electronic motor/
control with care.
- Unseated pins in wiring harness connectors.- Check for unseated pins in connectors on motor harness.
- Bad motor/ control module.- Test with a temporary jumper between R - G.
- Moisture present in motor or control module.
- Motor rocks, but won’t start.- Loose motor mount.- Check for loose motor mount.- Turn power OFF prior to repair.
- Blower wheel not tight on motor shaft.- Make sure blower wheel is tight on shaft.Wait 5 minutes after disconnecting power before opening motor.
- Bad motor/ control module.- Perform motor/ control replacement check, ECM motors only.- Handle electronic motor/ control with care.
- Motor oscillates up & down while being tested off of blower.- It is normal for motor to oscillate with no load on shaft.
- Motor starts, but runs erratically.- Varies up and down or intermittent.- Variation in 230 Vac to motor.- Check line voltage for variation or “sag".- Turn power OFF prior to repair.
- Unseated pins in wiring harness connectors.- Check low voltage connections (G, Y, W, R, C) at motor, unseated pins in motor harness connectors.
- Erratic CFM command from "BK" terminal.- Check-out system controls - Thermostat.
- Improper thermostat connection or setting.- Perform Moisture Check.
- Moisture present in motor/ control module.
- "Hunts" or "puffs" at high CFM (speed).- Incorrect or dirty filters).- Does removing panel or filter reduce "puffing’’?- Turn power OFF prior to repair.
- Incorrect supply or return ductwork.- Check/ replace filter.
- Incorrect blower speed setting.- Check/ correct duct restrictions.
- Adjust to correct blower speed setting.
- Motor starts, but runs erratically.- Stays at low CFM despite system call for cool or heat CFM.- 24 Vac wires miswired or loose.- Check low voltage (Thermostat) wires and connections.- Turn power OFF prior to repair. Wait 5 minutes after disconnecting power before opening motor.
- "R" missing/ not connected at motor.- Verify fan is not in delay mode - wait until delay complete.- Handle electronic motor/ control with care.
- Fan in delay mode.- Perform motor/ control replacement check. ECM motors only.
- Stays at high CFM.- "R" missing/ not connected at motor.- Is fan in delay mode? - wait until delay time complete.- Turn power OFF prior to repair. Wait 5 minutes after disconnecting power before opening motor.
- Fan in delay mode.- Perform motor/ control replacement check. ECM motors only.- Handle electronic motor/ control with care.
- Blower won’t shut off.- Current leakage from controls into G, Y, or W.- Check for Triac switched t'stat or solid state relay.- Turn power OFF prior to repair.
- Excessive noise.- Air noise.- High static creating high blower speed.- Check/ replace filter.- Turn power OFF prior to repair.
- Incorrect supply or return ductwork.- Check/ correct duct restrictions.
- Incorrect or dirty filter(s).- Adjust to correct blower speed setting.
- Incorrect blower speed setting.
- Noisy blower or cabinet.- Loose blower housing, panels, etc.- Check for loose blower housing, panels, etc.- Turn power OFF prior to repair.
- High static creating high blower speed.- Check for air whistling thru seams in ducts, cabinets or panels.
- Air leaks in ductwork, cabinets, or panels.- Check for cabinet/ duct deformation.
- "Hunts" or "puffs" at high CFM (speed).- High static creating high blower speed.- Does removing panel or filter reduce "puffing"?- Turn power OFF prior to repair.
- Incorrect or dirty filter(s).- Check/ replace filter.
- Incorrect supply or return ductwork.- Check/ correct duct restrictions.
- Incorrect blower speed setting.- Adjust to correct blower speed setting.
- Evidence of Moisture.- Motor failure or malfunction has occurred and moisture is present.- Moisture in motor/ control module.- Replace motor and perform Moisture Check.- Turn power OFF prior to repair. Wait 5 minutes after disconnecting power before opening motor.
- Handle electronic motor/ control with care.

Goodman N2H3 Heat Pump Troubleshooting

Status LEDStatus LED DescriptionStatus LED Troubleshooting Information
Green “POWER”Module has powerSupply voltage is present at module terminals
Red “TRIP”Thermostat demand signal Y1 is present, but the compressor is not running1. Compressor protector is open
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. Low pressure switch open if present in system
6. Compressor contactor has failed open
Yellow “ALERT” Flash Code 1Long Run Time Compressor is running extremely long run cycles1. Low refrigerant charge
2. Evaporator blower is not running
3. Evaporator coil is frozen
4. Faulty metering device
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in system)
7. Thermostat is malfunctioning
Yellow “ALERT” Flash Code 2System Pressure Trip Discharge or suction pressure out of limits or compressor overloaded1. High head pressure
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3. Condenser fan is not running
4. Return air duct has substantial leakage
5. If low pressure switch present in system, check Flash Code 1 information
Yellow “ALERT” Flash Code 3Short Cycling Compressor is running only briefly1. Thermostat demand signal is intermittent
2. Time delay relay or control board defective
3. If high pressure switch present go to Flash Code 2 information
4. If low pressure switch present go to Flash Code 1 information
Yellow “ALERT” Flash Code 4Locked Rotor1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Yellow “ALERT” Flash Code 5Open Circuit1. Outdoor unit power disconnect is open
2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
4. High pressure switch is open and requires manual reset
5. Open circuit in compressor supply wiring or connections
6. Unusually long compressor protector reset time due to extreme ambient temperature
7. Compressor windings are damaged
Yellow “ALERT” Flash Code 6Open Start Circuit Current only in run circuit1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
3. Compressor start winding is damaged
Yellow “ALERT” Flash Code 7Open Run Circuit Current only in start circuit1. Open circuit in compressor run wiring or connections
2. Compressor run winding is damaged
Yellow “ALERT” Flash Code 8Welded Contactor Compressor always runs1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
Yellow “ALERT” Flash Code 9Low Voltage Control circuit < 17VAC1. Control circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)